La valvola di protezione dai guasti FSV-1 qui descritta deve essere installata e sottoposta a manutenzione conformemente alle istruzioni contenute nel presente documento, nonché in conformità alle normative applicabili della National Fire Protection Association e alle normative emanate dalle autorità competenti in materia.The Model FSV-1 Fail-Safe Valve described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction.
Per qualsiasi domanda rivolgersi all'installatore o al costruttore degli sprinkler.The installing contractor or sprinkler manufacturer should be contacted with any questions.
All'attivazione della valvola DV-5, la tubazione a valle della valvola DV-5 viene pressurizzata.Upon operation of the DV-5 Valve, the piping downstream of the DV-5 Valve becomes pressurized.
Alla sua attivazione, la valvola FSV-1 farà in modo che la pressione della camera a mem brana DV-5 venga rilasciata nell'atmosfera più velocemente di quanto possa essere ripressurizzata attraverso il foro da 3,2 mm (1/8") nella connessione dell'alimentazione della membrana alla valvola DV-5.Upon operation, the FSV-1 will vent the DV-5 Diaphragm Chamber to atmosphere quicker than it can be repressurized through the 3,2 mm (1/8") restriction in the diaphragm supply connection to the DV-5.
La seguente procedura d'ispezione deve essere eseguita come indicato e in conformità con i requisiti specifci NFPA.The following inspection procedure must be performed as indicated, in addition to any specific requirements of the NFPA, and any impairment must be immediately corrected.
Per qualsiasi domanda rivolgersi all'installatore o al costruttore del prodotto.The installing contractor or product manufacturer should be contacted relative to any questions.
Si consiglia di afdare i lavori di ispezione, collaudo e manutenzione a prestatori di servizi d'ispezione qualifcati conformemente alle disposizioni locali e/o nazionali.It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.
Non tentare di riparare una valvola di protezione dai guasti FSV-1 danneggiata.No attempt is to be made to repair an impaired Model FSV-1 Fail-Safe Valve.
L'intero gruppo deve essere sostituito in caso di malfunzionamento.The complete assembly must be replaced if their is indication of malfunction.
Prima di chiudere la valvola di controllo principale di un sistema antincendio, per eseguire lavori di ispezione o manutenzione su di esso, è necessario chiedere in anticipo l'autorizzazione alle autorità competenti prima di disattivare il sistema antincendio in questione e avvertire il personale su cui tale intervento potrebbe avere un effetto.Before closing a fire protection system control valve for inspection or maintenance work on the fire protection system that it controls, permission to shut down the effected fire protection system must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified.
La valvola FSV-1 deve essere ispezionata trimestralmente conformemente alle seguenti istruzioni ed eventuali danneggiamenti devono essere corretti sostituendo la valvola FSV-1.The Model FSV-1 Fail-Safe Valve must be inspected quarterly in accordance with the following instructions, and any impairment must be corrected by replacing the FSV-1.
In posizione di settaggio non ci dovrebbero essere perdite d'acqua dalla connessione di uscita allo scarico.When in the set position there should not be any water leakage from the outlet connection to drain.
Nessuna garanzia viene data per prodotti o componenti fabbricati da imprese non afliate a TFBP in relazione alla proprietà o per prodotti e componenti sottoposti a uso improprio, installazione non corretta, corrosione, oppure per prodotti che non sono stati installati, sottoposti a manutenzione, modifcati o riparati conformemente alle norme applicabili della “National Fire Protection Association" e/o alle norme emanate da altre autorità competenti in materia.No warranty is given for products or components manufactured by companies not affiliated by ownership with TFBP or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction.
I materiali considerati difettosi da TFBP saranno riparati o sostituiti a sola discrezione di TFBP.Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP' sole option.
TFBP declina ogni responsabilità per gli errori di progettazione degli sprinkler o per le informazioni inaccurate o incomplete fornite dall'Acquirente o dai rappresentanti dell'Acquirente.TFBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives.
In nessun caso TFBP sarà ritenuta responsabile, per contratto, illeciti civili o responsabilità oggettiva (strict liability) o in virtú di qualunque altra teoria legale, per danni incidentali, indiretti, speciali o consequenziali, tra cui le spese di manodopera, a prescindere dal fatto che TFBP sia stata informata della possibilità di tali danni. In nessun caso la responsabilità di TFBP sarà superiore al prezzo di vendita del prodotto.In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP' liability exceed an amount equal to the sales price.